Short answer
Size for the highest shaft power across the permitted curve.
Check maximum impeller diameter, end-of-curve flow and highest specific gravity, then add the selection margin.
| Motor rating | API 610 minimum factor | Industry practice, ANSI / ISO process pumps |
|---|---|---|
| < 22 kW (< 30 hp) | 125% of rated pump power | +15–25% over maximum pump power |
| 22–55 kW (30–75 hp) | 115% | +10–15% |
| > 55 kW (> 75 hp) | 110% | +5–10% |
The 1.15 service factor is an overload reserve. Use rated output to select the motor for normal operation.
1. Calculate shaft power
Read η from the curve at the duty point, speed and impeller diameter being purchased.

Pump BHP, Shaft Power & Motor Sizing Calculator
Write down which power the curve reports. Hydraulic power is the energy added to the liquid. Pump shaft power divides that hydraulic power by pump efficiency. Electrical input includes the motor and any drive losses. A meter on the supply side gives electrical input, while the motor nameplate kW is the rated mechanical output. Comparing those numbers directly without tracking the boundary can give the wrong selection. Record the duty point, impeller trim and rotation speed next to the efficiency used in the calculation.
2. Find the highest power the pump can draw
| Operating case | Why it matters |
|---|---|
| End-of-curve flow | Read absorbed power at the highest permitted flow. |
| Maximum impeller diameter | Larger diameters raise shaft demand. |
| Highest specific gravity | At the same duty and efficiency, shaft demand scales with density. |
| Highest viscosity | Read the corrected curve and use the corrected efficiency. |
| Water commissioning | Check the temporary duty, valve position and power on the water curve. |
In the Hydraulic Institute example, a pump that draws 25–30 hp at rated flow can require a 40 hp motor to cover the end of the curve.
Lay the required flow range over the manufacturer's absorbed-power curve. Start at minimum process flow, mark the normal and rated points and carry the review through the highest permitted flow. Record the maximum demand along that path. Repeat the comparison for the largest permitted impeller and highest liquid density the pump can see in normal operation. Viscous cold-start conditions need their own curve or correction. A low liquid temperature can change both hydraulic performance and the power needed to reach running speed.
A water commissioning run can use a different point on the system curve. Record the valve position, flow restriction, impeller and test fluid before energizing. Keep the water run and process duties as separate cases on the driver selection sheet. This makes it clear which case sets the maximum continuous demand and which requires a separate start or protection check.
3. The specific-gravity trap
| Liquid | Relative shaft power |
|---|---|
| Water, SG 1.00 | 1.00× |
| 98% sulfuric acid, SG 1.84 | 1.84× |
A pump absorbing 22 kW on water absorbs 40.5 kW on 98% sulfuric acid at the same flow, head and efficiency. How Specific Gravity Affects Centrifugal Pump Power.
4. Derate for site conditions
| Ambient temperature | ABB motor output factor | Site elevation | ABB motor output factor |
|---|---|---|---|
| ≤ 40 °C | 1.000 | ≤ 1,000 m | 1.00 |
| 45 °C | 0.965 | 1,500 m | 0.96 |
| 50 °C | 0.930 | 2,000 m | 0.92 |
| 55 °C | 0.900 | 2,500 m | 0.88 |
| 60 °C | 0.865 | 3,000 m | 0.84 |
Multiply the applicable motor factors for a combined screening check. Check drive output current separately. For ABB ACS880-01 units subject to the standard altitude rule, the output current falls 1% per 100 m above 1,000 m. The factor at 1,500 m is 0.95.
Use the nameplate output as the starting point and obtain the permitted output from the motor supplier for the specified enclosure, cooling method and insulation system. Convert the site elevation and the air temperature at the motor intake into capacity factors on the same rating basis. The standard factor at or below the baseline is the reference. High elevation reduces cooling air density, and hot intake air reduces the temperature difference available to carry heat away. Where both conditions apply, record the combined site rating and carry that value into the comparison with required shaft power.
Compare continuous output at the site before applying the motor manufacturer's overload information. Keep motor derating and drive current derating on separate lines in the calculation. A drive that meets the kW headline can reach its current or thermal limit at elevation. Give the drive supplier the required continuous current, start profile, cable length, switching frequency and ventilation arrangement. Ask for the continuous output and permissible short-time overload for the exact drive ordered.
5. Worked example: 37 kW or 45 kW?
At 150 m³/h and 45 m head, with ρ = 1,200 kg/m³ and efficiency 0.72, hydraulic power is 22.06 kW and shaft power is 30.65 kW (41.1 hp). The curve ends at 34.0 kW. With the 10% selection margin, size for 37.4 kW.
| Motor | Rated output | Decision |
|---|---|---|
| 37 kW IEC | 37.00 kW | Too small |
| 50 hp NEMA | 37.29 kW | Too small |
| 45 kW IEC | 45.00 kW | Select |
| 60 hp NEMA | 44.74 kW | Select |
At 2,000 m and 45 °C, the ABB factors for this check are 0.92 and 0.965. A 45 kW motor provides 39.95 kW, above 37.4 kW. A 37 kW motor provides 32.85 kW and falls below the 34.0 kW end-of-curve demand.
Follow the comparison in this order: calculate hydraulic output, divide by curve efficiency, find the maximum shaft power over the curve, then apply the applicable selection margin. The required output is set by the curve end in this case. The 37 kW nameplate is close to the result but below it, and the 50 hp option also falls below it when converted on the same basis. The 45 kW and 60 hp ratings both clear the requirement at the reference conditions. When selecting the hardware for a hot elevated site, compare the derated output with the same calculated demand. A change in the site factors changes the available output, while the pump curve still sets the load.
5a. Standard motor ratings: pick the next size up
| IEC power (kW) | Common NEMA comparison (hp) | NEMA output (kW) |
|---|---|---|
| 0.75 | 1 | 0.75 |
| 1.1 | 1.5 | 1.12 |
| 1.5 | 2 | 1.49 |
| 2.2 | 3 | 2.24 |
| 3 | 5 | 3.73 |
| 4 | 7.5 | 5.59 |
| 5.5 | 7.5 | 5.59 |
| 7.5 | 10 | 7.46 |
| 11 | 15 | 11.19 |
| 15 | 20 | 14.91 |
| 18.5 | 25 | 18.64 |
| 22 | 30 | 22.37 |
| 30 | 40 | 29.83 |
| 37 | 50 | 37.28 |
| 45 | 60 | 44.74 |
| 55 | 75 | 55.93 |
| 75 | 100 | 74.57 |
| 90 | 125 | 93.21 |
| 110 | 150 | 111.85 |
| 132 | 200 | 149.14 |
| 160 | 250 | 186.42 |
| 200 | 300 | 223.71 |
| 250 | 350 | 260.99 |
| 315 | 450 | 335.56 |
A 50 hp motor gives 37.29 kW. Compare ratings in kW and round up after determining required output. At the same frequency a four-pole motor runs at roughly half the speed of a two-pole motor. At half speed, the affinity relationships give one-quarter head and one-eighth shaft power at corresponding points.
5b. Efficiency class
| Four-pole class, 50 Hz | 11 kW | 45 kW | 110 kW |
|---|---|---|---|
| IE2 | 89.8% | 93.1% | 94.5% |
| IE3 | 91.4% | 94.2% | 95.4% |
| IE4 | 93.3% | 95.4% | 96.3% |
A lower-slip replacement motor can run faster at the same mains frequency. A 0.5% speed increase raises shaft demand by approximately 1.5% at corresponding points. Recheck the duty after replacing the motor.
Compare motor efficiency at the same output, frequency and pole count. The class table gives minimum nominal efficiencies for the stated nameplate conditions. Ask for the selected motor's published full-load and part-load values so the electrical input estimate can use the actual expected shaft load. A purchase comparison should also record which duty periods are continuous and which are occasional. That information helps explain the expected energy use without substituting an unrelated motor rating.
Keep the hydraulic and electrical effects separate when replacing a motor. A change in slip changes actual pump speed and therefore can move the operating point on both the pump and system curves. Check the speed printed on the replacement nameplate against the curve basis. Compare the resulting head and absorbed power at corresponding points and then check the actual operating point. A minor speed change matters when the original driver had little unused capacity.
6. Check starting and VFD speed limits
- At corresponding points, centrifugal-pump load torque rises approximately with the square of speed. Check acceleration with the selected starter and pump start-up sequence.
- Check starting separately for high rotating inertia, viscous cold starts or frequent starts.
- Above rated speed, use the pump affinity laws calculator. Raising 50 Hz to 55 Hz raises the speed-cubed demand to 1.331 times the original. At 52 Hz the factor is 1.125. Check motor ventilation at low speed.
Evaluate the start against the torque and current the installation can supply. Compare the motor torque curve with the pump load and rotor inertia from standstill through rated speed. Select direct starting or a reduced-voltage arrangement from that comparison and the plant supply limits. Document the permitted acceleration time and the interval between starts so protection can distinguish a normal acceleration from a stalled or slow start.
Set the upper frequency after comparing shaft power, casing pressure, suction conditions and the selected pump curve at that speed. A change in speed moves the system duty as well as the pump curve. At low speed, check motor cooling, pump minimum flow and the seal support circuit. Record ramp settings, motor protection data and the permitted speed band on the commissioning sheet so subsequent changes can be assessed against the driver and pump limits.
Starting checks
7. Check mechanical fit before changing rating
Compare the two outline drawings for shaft centre height, foot drilling, shaft extension diameter and length, and coupling gap. Include baseplate work in the price when the replacement frame changes.

Put the two motor outline drawings alongside the baseplate and coupling arrangement. Compare frame dimensions, foot hole centers, shaft height and the shaft extension as a set. A motor can satisfy the power calculation and still require machining, a different coupling hub or a baseplate change. Include the installed coupling separation, guard space and access for alignment and removal in the replacement scope.
8. Reusing an existing motor on a replacement pump
- Confirm that site-rated output covers the new pump’s highest specific-gravity duty, end-of-curve power and selection margin.
- Match the nameplate speed to the proposed pump curve.
- Match the frame, shaft extension, coupling and baseplate.
Start with a readable nameplate and the installed motor outline drawing. Record rated output, full-load speed, voltage, frequency and enclosure alongside the existing starter or drive model. Ask the supplier for the selected pump curve and greatest shaft demand across the allowable flow range at the actual liquid density. Compare that demand with available site output and document the mounting and coupling fit. If any of those checks fails, price the revised motor, coupling, guard and baseplate work as part of the pump replacement.
Frequently asked questions
How much margin should a pump motor have?
Industry practice for ANSI and ISO process pumps: add 15–25% over maximum pump power below 22 kW, 10–15% from 22 to 55 kW, and 5–10% above 55 kW. API 610 gives minimum factors of 125%, 115% and 110% of rated pump power for the corresponding motor rating bands.
Should the motor cover the maximum impeller?
Yes. Size for the maximum permissible impeller diameter if the driver must cover larger impellers later in service.
Can I count the 1.15 service factor as margin?
No. Use the motor nameplate output for normal selection. Reserve service factor for the motor’s permitted overload conditions.
Does a bigger motor use more electricity?
The pump and system set the shaft load. Electrical input is shaft load divided by motor efficiency at that load. Compare the two part-load efficiency curves.
Can a VFD fix an undersized motor?
A VFD can reduce shaft demand by slowing the pump, which reduces flow and head. At the original duty point the motor remains undersized.
Can I size the motor from current alone?
No. Current describes today’s operating point. Check the maximum shaft demand across the permitted curve and liquid conditions.
References
- Source: API 610, 11th edition, Table 12, motor power ratings.
- Source: ABB Low Voltage Motors Motor Guide, October 2018, Table 4.1.
- Source: ABB ACS880-01 hardware manual, technical data: altitude derating.
- Source: ABB TM025, August 2014, Table 2 (IEC 60034-30-1 50 Hz efficiency classes).
- Source: Hydraulic Institute Pump FAQs, pump power requirements.
ANSI Pumps Pro engineering team, Zibo, China — manufacturing ANSI B73.1 pumps and parts since 2010